COMPARISON OF GRP/FRP CABLE TRAYS V/S METAL CABLE TRAYS


1.Corrosion Resistance
GRP/FRP - Excellent corrosion resistance against sea water and most chemical fumes
METAL - Poor corrosion resistance, pitting takes place even in SS or aluminum in sea water. Galvanic Corrosion takes place between Stainless Steel trays and MS supports

2.Hot Working
GRP/FRP -No Hot working, all assembly by Nut & Bolts
METAL -Hot working , welding cutting and joining requires special permission in hazardous areas

3.Light weight
GRP/FRP -
Sp.gr. 1.9, 1/4th that of steel, even lighter than Aluminum(sp.gr.2.8), just one person required to lift a big size cable ladder, so very easy and fast Installation, saving time and money
METAL -Very heavy, 4 times to GRP/FRP, hence crane or 3 people required to lift a cable ladder

4.Fire Retardant
GRP/FRP -
Meets most stringent offshore fire resistance norms as per British, ASTM and UL specifications
METAL -In heavy fire even steel de-shapes and needs replacement

5.Installation Cost
GRP/FRP -
Very low, as lighter in wt hence only one man can lift, and very easy to cut and fabricate at site, thus faster installation and easy site adjustment and modifications
METAL -HIGH, needs 2-3 persons or special equipment to lift, also difficult to cut and refabricate as per site requirement as cutting takes time.

6.Risk of cable damage
GRP/FRP -
Very low, as being plastics have much less hardness and even its sharp edges cannot damage a cable
METAL -When any site modification is done, sharp edges are created in metal which can cause damage to cables and pose risk of current.

7.High insulation ands Safe
GRP/FRP -
No earthing of cable tray is required as it has high Insulation value. In case of any cable stripping, the tray being Insulated is safe for the Humans.
METAL -Earthing is must, hence cost of earthing increases overall cost, which is not generally considered when evaluating.

8.Part consolidation
GRP/FRP -
As GRP/FRP is extruded section, inbuilt ribs for reinforcement, collars for fixing covers are possible in single section
METAL -This is not possible in metal, and if welding is done it looks very bad.

9.U.V. resistance
GRP/FRP -
All GRP/FRP cable Trays are made from very high U.V. additives, in addition to special surfacing Veils for glass blooming prevention, and carbon black for additional U.V protection
METAL -N/A

10.Antistatic
GRP/FRP - Cable trays are available in antistatic option as well for oil hazardous areas on demand, thus safe even in hydrocarbon atmosphere.
METAL -N/A

11.First Time COST
GRP/FRP - FRP/GRP cable trays are competitive to SS trays with all above advantages
METAL -SS trays are very costly compared to GRP/FRP Trays

Tuesday, June 19, 2007

THE 4-20mA CURRENT LOOP

THE 4-20mA CURRENT LOOP
The 4-2OmA current loop has been with us for so longthat it's become rather taken for granted in the industrialand process sectors alike. Its popularity comes from itsease of use and its performance. However, just becausesomething is that ubiquitous doesn't mean we're allnecessarily getting the best out of our current loops.
A big benefit of the current loop is its simple wiring justthe two wires. The supply voltage and measuring currentare supplied over the same two wires. Zero offset of thebase current (ie. 4mA) makes cable break detection simple:if the current suddenly drops to zero, you have a cable break.In addition, the current signal is immune to any stray electricalinterference, and a current signal can be transmitted overlong distances.







Typical wiring for current output transducer.
You can think of the current loop itself as being analogousto a water system. You have a hose pipe (the wires) anda source tap (the power supply). You have a spray gunthat regulates the flow (the transducer). You can haveother equipment on the line, but it all has to be connectedtogether in a ring Ioop. The more holes (devices) you haveon the hose pipe, the higher the pressure will be requiredfrom the tap. Relating all that back to the current loop,you see a power supply, a transducer and one or morepieces of instrumentation all connected together in a ring.
You'll often hear things referred to as being either activeor passive. Some instruments have an active output whichincludes both the control of the current in the loop as wellas provide the supply voltage. This is typically specifiedas being a 4-20mA output into 10-750 Ohms, or somethingsimilar. A passive input would be a simple resistor input thathas a voltage drop to be factored into the equation oncethe supply voltage is chosen. This is typically specified asa 4-20mA input into 10 Ohm.
Working out the power supply requirement is a simple matterof adding up all the units in the loop at maximum currentof 20mA. As an example, suppose you have a sensor'regulator' which requires minimum 12V DC and instrumentationof 10 Ohm input:
10 Ohm x 20mA = 0.2V
So, for this circuit, a 12.2V minimum supply is required, thesensor's maximum voltage might be specified at 30V, so a24V supply would be all the circuit requirements with sparecapacity to boot.
In order to measure the current loop it is necessary to breakthe loop and insert a current meter into it. You can alsomeasure the voltage across the various components by inthe loop, such as the voltage out of the power supply, thevoltage over a sensor, and the voltages over the variouspieces of instrumentation. This information will give you agood picture of what is happening within the loop.






Multi-instrument 4-20mA current loop with panel meter,chart recorder, computers, etc.
A question which is sometimes asked is whether it is possibleto use single power supply over several loops. This is possible,but you have to ensure that the power supply can give enoughcurrent to meet the needs of multiple loops. It is also thecase that the current loops will have the same zero negativereference, which can cause a ground loop. In addition,interference from one loop can affect all the other loopsdriven from the one supply.
This article is printed with the kind permission ofMorten Moller, who runs an internet support andconsultancy business and can be contacted atmorten@askmorten.co.ukHis website is at http://www.askmorten.co.uk/

Installation Detail/Hook-up

Installation Detail/Hook-up

Installation Detail atau sketch perlu memaparkan apa yang diperlukan untuk memasang sesuatu instrument.

Ini termasuk kesemua bahan (material) yang yang diperlukan untuk melengkapkan satu proses pemasangan (installation).
Maklumat dari pihak vendor adalah amat perlu bagi memastikan segala bahan yang diperlukan adalah sesuai dan sepadan dengan saiz connection yang diperlukan oleh instrument.

Designer jga perlu mengandaikan situasi dimana Tukang Pasang tidak biasa atau pertama kali memasang Instrument tersebut.

Sunday, May 27, 2007

NEMA Enclosure Types

NEMA PC Enclosure Types

This document provides general information on the definitions of NEMA Enclosure Types
Definitions[From NEMA 250-1997]
In Non-Hazardous Locations, the specific enclosure Types, their applications, and the environmental conditions they are designed to protect against, when completely and properly installed, are as follows:
Type 1 - The unit is constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment and to provide a degree of protection against falling dirt.
Type 2 - Enclosure constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment, to provide a degree of protection against falling dirt, and to provide a degree of protection against dripping and light splashing of liquids.
Type 3 - Pc cabinet constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust; and that will be undamaged by the external formation of ice on the enclosure.
Type 3R - Cabinet constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, and snow; and that will be undamaged by the external formation of ice on the enclosure.
Type 3S - Computer cabinet constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust; and in which the external mechanism(s) remain operable when ice laden.
Type 4 - Computer enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, and hose-directed water; and that will be undamaged by the external formation of ice on the enclosure.
Type 4X - protection unit constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, hose-directed water, and corrosion; and that will be undamaged by the external formation of ice on the enclosure.
Type 5 - computer enclosure constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against settling airborne dust, lint, fibres, and flyings; and to provide a degree of protection against dripping and light splashing of liquids.
Type 6 - PC Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against hose-directed water and the entry of water during occasional temporary submersion at a limited depth; and that will be undamaged by the external formation of ice on the enclosure.
Type 6P - cabinet constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against hose-directed water and the entry of water during prolonged submersion at a limited depth; and that will be undamaged by the external formation of ice on the enclosure.
Type 12 - computer cabinet constructed (without knockouts) for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibres, and flyings; and against dripping and light splashing of liquids.
Type 12K - Enclosures constructed (with knockouts) for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibres, and flyings; and against dripping and light splashing of liquids.
Type 13 - Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibres, and flyings; and against the spraying, splashing, and seepage of water, oil, and non-corrosive coolants.

PC Enclosure Classification Designations
IEC Publication 60529 Classification of Degrees of Protection Provided by Enclosures provides a system for specifying the enclosures of electrical equipment on the basis of the degree of protection provided by the enclosure. IEC 60529 does not specify degrees of protection against mechanical damage of equipment, risk of explosions, or conditions such as moisture (produced for example by condensation), corrosive vapours, fungus, or vermin. The NEMA Standard for Enclosures for Electrical Equipment does test for environmental conditions such as corrosion, rust, icing, oil, and coolants. For this reason, and because the test and evaluations for other characteristics are not identical, the IEC Enclosure Classification Designations cannot be exactly equated with the enclosure Type numbers in this Standard.
The IEC designation consists of the letters IP followed by two numerals. The first characteristic numeral indicates the degree of protection provided by the enclosure with respect to persons and solid foreign objects entering the enclosure. The second characteristic numeral indicates the degree of protection provided by the enclosure with respect to the harmful ingress of water.
Table A-1 provides an equivalent conversion from the enclosure Type numbers in this Standard to the IEC Enclosure Classification Designations. The enclosure type numbers meet or exceed the test requirements for the associated IEC Classification; for this reason Table A-1 cannot be used to convert from IEC Classifications to enclosure Type numbers.
Table A-1 [From NEMA 250-1997]
Conversion of Enclosure Type numbers to IEC Classification Designations
Cannot be used to convert IEC Classification Designations to NEMA Type numbers



Enclosure

NEMA -IEC IP


1 -IP10

2 -IP11

3 -IP54

3R- IP14

3S -IP54

4 and 4X- IP56

5 -IP52

6 AND 6P- IP67

12 AND 12K -IP52

13- IP54